Floating roof storage tank boilover

Title

Floating roof storage tank boilover

Subject

ADCO
Boilover
Experiment
Fire
Tank
Theory

Description

Storage tanks are important facilities for the major hazard installations (MHIs) to store large quantity of crude oil. There is several fire types can occur with large diameter open top floating roof storage tanks. Boilover is considered one of the most dangerous fires in large-scale oil tank. The world has witnessed many incidents due to boilover in floating roof storage tank. Boilover problem has been studied in experiments and by models to understand how to control the boilover phenomena. An experimental study has been carried out in Jebel Dhanna (JD) terminal area by Abu Dhabi Company for Onshore Oil Operations (ADCO) with support of Resource Protection International (RPI) consultant. 2.4m diameter and 4.5m diameters pans have been used to study the characteristics of the large oil-tank fires (i) to gain more knowledge of the boilover phenomenon of crude oil (ii) verify if the crude oil stored by ADCO would boilover (ii) estimation of rate of hot-zone growth and the period needed from ignition to boilover (iii) estimation of radiant heat and consequences of boilover. This paper presents an overview on the floating roof storage tank boilover. The paper also presents briefly boilover experimental research study carried out by ADCO.

Publisher

Journal of Loss Prevention in the Process Industries

Date

2011-01-01

Contributor

Shaluf, Ibrahim M.
Abdullah, Salim A.

Type

Journal Article

Identifier

SIELG29P
0950-4230
10.1016/j.jlp.2010.06.007

Collection

Citation

“Floating roof storage tank boilover,” Lamar University Midstream Center Research, accessed May 15, 2024, https://lumc.omeka.net/items/show/1428.

Output Formats